No. | Item | Qty | Note |
1 | Wi-Fi Energy Meter | 1 | WiFi module embedded |
2 | Split-Core CT (Current Transformer) | 1 | 150A or 250A Optional |
3 | 2.4G Antenna | 1 | External Panel Antenna |
Specification | Description |
Standard package | 1. Wi-Fi Energy Meter (WEM3080) x 1 |
2. Split-core Current Transformer (150A or 250A optional) x 3 | |
3. 2.4G Wi-Fi Antenna x 1 | |
Phase | Three phase |
Power Supply | Built-in universal power supply |
Communication | Built-in Wi-Fi |
Antenna | External 2.4G antenna with SMA male |
Reporting interval | 1-5 minutes interval, typically 1 minute |
Report contents | Active Energy (Forward and Reverse), Active Power, Voltage, Current, Frequency |
Configuration | 1. Wi-Fi access point and webpage for setting SSID and password |
2. Mobile App for setting SSID and password | |
Monitoring Scenarios | 1. Monitor on Iammeter Cloud |
2. Monitor locally on your PC via WLAN (Http get interface) | |
3. Integrate with third party server, such as your own server, PVoutput and HomeAssistant (TCP/SSL interface) |
Specification | Description |
Input Voltage | 80V~277VAC (Phase Voltage), 140V~480 VAC (Line Voltage) |
CT Rating | 100A or 250A optional |
Measurement Accuracy | 1. Voltage: ±1.0% |
2. Current: ±1.0% | |
3. Active Power: ±1.0% | |
4. Active Energy: Class 1 as defined by IEC62053-21 | |
Typical power consumption | ≤2W(220VAC input) |
Specification | Description |
Weight | 0.5kg |
Dimension | 90.2*71*57.5mm (2 DIN pole) |
Protection | IP51 |
Connection | AC input: UA-Live wire Phase A, UB-Live wire Phase B, UC-Live wire Phase C, UN-Neutral wire |
RS485 interface: A-Positive, B-Negative | |
CT: IA+ is Positive Phase A, IA- is Negative Phase A; IB+ is Positive Phase B, IB- is Negative Phase B; IC+ is Positive Phase A, IC- is Negative Phase C | |
SMA port: External Antenna Port |
Specification | Description |
Operating Temperature | -20~+60℃ |
Operating Humidity | 5~95% |
Altitude | 0~3000m |
Specification | Description |
WLAN | Channel:Auto |
Security:WPA2-PSK | |
SSID | iMeter_xxxxxxxxx(8 digits serial no), no password |
Configuration page | URL:http://11.11.11.1 |
Login username: admin | |
Password:admin |
Specification | Description |
Wi-Fi Mode | IEEE802.11b/g/n, Wi-Fi Channel 1-13 |
Transmit power | 18.5dBm@11b,16.5dBm@11g,15.5dBm@11n; |
Wi-Fi Frequency | 2.412 ~ 2.484GHZ |
Transmit Speed | 72.2Mbps@20M Bandwidth; 150Mbps@40M Bandwidth |
Maximum Connections | 8 |
Wi-Fi Antenna | External, 8dBi gain |
Specification | Description |
Protocol | Modbus-RTU |
Data format | “n,8,1” |
Baud rate | 1200、2400、4800、9600Bps;9600Bps by default |
Indicator | Description |
RUN | Always on after powering on,flashing while the WiFi module is communicating with the power meter |
REV | Always on when the current is reversed as per the bottom-marked current direction of CT for any phase, or it is connect to the wrong phase (Like you connect CT to the Phase A, but you measure the current of Phase B) |
WIFI | Always on after the Wi-Fi module is connected to the router |
Essential Requirements | Applied Standard |
Health and Safety | EN60950-1:2006+A11; 2009+A1;2010+A12;2011+A2;2013 |
Electromagnetic Compatibility | EN62311:2008 |
Effective Use of the Radio Spectrum | 1. ETSI EN 301 489-1 V2.1.1 (2017-02) |
2. ETSI EN 301 489-1 V3.1.1 (2017-02) | |
3. ETSI EN 300 328 V2.1.1 (2016-11) |
Essential Requirements | Applied Standard | Meters of Class |
General Requirement | IEC62052-11 | Protective classⅠ, Indoor |
Accuracy requirement | IEC62053-21 | Accuracy index class 1 |
Mechanical requirement | IEC62053-21 | Protective classⅠ, Indoor |